GlobeCore’s US-6S oil and gas industry transformers vacuum drying is a piece of kit that has been found to be very useful in the process of removing moisture in transformer windings used in oil and gas production and transportation facilities. In these industries, transformers work in tough conditions and provide a steady power supply for important processes. It is important to note that if moisture builds up in a transformer when it is in use or stored, there is a possibility that this could reduce the insulation levels and increase the risk of short circuits. The US-6S creates a vacuum inside the drying chamber, which allows moisture to evaporate efficiently, even from hard-to-reach areas, without damaging insulation materials. It’s got a sealed chamber, a strong vacuum pump and an automatic temperature and pressure control system to make sure it dries evenly and safely. The US-6S from GlobeCore is a reliable solution for the oil and gas industry that extends the service life of transformers, increases their reliability and ensures uninterrupted power supply at critical infrastructure facilities.
Oil and gas industry transformers vacuum drying US-6S Specifications
No. | Parameter | Value |
Drying chamber | ||
1 | Internal dimensions, mm, max | |
– depth | 2,000 | |
– width | 1,300 | |
– height | 1,600 | |
Heating section | ||
2 | Heater power, kW | 45 |
3 | Temperature adjustment range, °С | 20…120 |
4 | Quantity of thermal electric heaters, pcs | 15 |
Vacuum section | ||
5 | Capacity, m3/h | 1,000 |
6 | Total power level of engines, kW | 11 |
7 | Achieved vacuum level, mbar | 1 |
Circulation system | ||
8 | Capacity, m3/h | 2,000 |
9 | Fan power, kW | 2.2 |
Exhaust system | ||
10 | Capacity, m3/h | 2,000 |
11 | Fan power, kW | 1.1 |
Condensation system | ||
12 | Chiller power, kW | 3.0 |
13 | Cooling performance of chiller, kcal/h | 6,000 |
14 | Condensation area, m2 | 7.5 |
15 | Heat exchanger (condenser) type | shell-and-tube |
Pneumatic system | ||
16 | Compressor power, kW | 1.1 |
17 | Pressure, bar | 9 |