CMM-4 Portable Unit for Powered Transformer Oil Purification

Oil Purification Plant Globecore CMM-4 may be used for:

(1) heating electrical equipment that contains dielectric insulating oil with hot oil;

(2) for vacuum drying of transformers; and

(3) for vacuumizing.

The unit is best suited to facilities that install, repair and service oil filled electric power transformers and other oil filled electrical equipment.

portable oil plant for Oil Purification

Oil Purification Plant

 

Parameter Value
Oil Purification Capacity, m3/hour / gals. per hour:
  • oil degassing, nitrogenation, oil drying and oil filtration mode
4/1059.0
  • heating and filtration mode
7/1853.0
Capacity adjustment range, m3/hour / gals. per hour 0-4/0-1059.0
Processed oil parameters (after Oil Purification)*:
  • mass moisture content, g/ton, max
10
  • ISO 4406 purity class
9
  • solid particle content, g/ton, max
8
  • filtration fineness, micron
5
  • dielectric strength, kV, min
70
Oil temperature in oil heating mode, ºС/ ºF 90/184
Oil Filtration rate ≥50
Outlet pressure, Mpa 0.35
Oil output head, meters 35.0
Oil heater power, kW 55
Oil heater mean surface power, W/cm2, max 1.15
Max power consumption, kW
Electric power
  • voltage, V
380
  • AC frequency, Hz**
50/60
Dimensions, mm/ft
  • length
1650/5’5’’
  • width
1250/5’3’’
  • Height
1650/4’1’’
Weight, kg/lbs 50/2,033.2

Note: * initial oil parameters:

  • volumetric gas content – below 5%
  • mass moisture content – below 0.01% (100 g/ton)
  • temperature – above 0 ºС/ 32 ºF.

**All equipment sold in the USA is designed to operate on 60 Hz AC Power