Power Transformer
What does an insulation power factor test on a transformer indicate?
- 该话题包含 1个回复,2 人参与,最后由 更新于 1周、 4天前 。
Answers
-
一月 19, 2026 2:46 下午 by Plinio Leiva-Bou
An insulation power factor test indicates dielectric quality and loss characteristics of oil-paper insulation, bushings, and windings. Elevated power factor reflects moisture ingress, contamination, thermal aging, or partial discharge precursors. Utilities trend results over time to decide when oil processing, drying, or refurbishment is needed. A low and stable value indicates healthy insulation and acceptable dielectric margins for service.