Power Transformer
what is magnetic balance test in power transformers?
- 该话题包含 1个回复,2 人参与,最后由 更新于 3天、 20小时前 。
Answers
-
一月 26, 2026 8:07 下午 by Amanda Moore
The magnetic balance test is used on three phase transformers to check core integrity and detect inter turn or inter phase faults. With the test, a single phase voltage is applied to one phase and induced voltages are measured in the other phases. In a healthy transformer, the measured voltages follow characteristic patterns depending on the connection group. Significant deviations indicate possible issues such as core damage, shorted turns or incorrect connections. It is a simple offline diagnostic that helps verify magnetic circuit symmetry after transport or repair.