GlobeCore can supply an online moisture + temperature probe with a local display for integration into a mobile transformer oil purification plant. On GlobeCore CMM mobile purification plants, the optional moisture probe provides continuous transformer-oil moisture and temperature measurement, and the plant can be supplied with a display showing moisture in ppm. For your application, I’d recommend an online “moisture-in-oil” sensor that measures water activity (aw) + oil temperature and calculates moisture in ppm (this is the standard approach used in GlobeCore’s TOR moisture measurement concept).
Pole units may be swapped in hours; substation or GSU units require days to months depending on diagnostics, logistics, spares, and procurement.
Laminated silicon steel cores or amorphous metal, copper/aluminum windings, cellulose insulation, mineral or ester dielectric oil, bushings, tap changers, cooling radiators.
一月 27, 2026 8:17 下午 回复至: Why the no-load power factor of an induction motor / transformer is very low? #332313No-load current is mostly magnetizing and reactive, delivering little real power. Core excitation dominates, making PF typically 0.05-0.2 lagging.
一月 26, 2026 12:39 下午 回复至: Why is a power factor transformer test performed during diagnostics? #332041Same principle as above: evaluates insulation system condition to predict service life and prevent catastrophic failure.
Repairs begin with diagnostics (DGA, IR, tan-delta, winding resistance, FRA), oil draining, tank opening, core-coil inspection, rewinding or insulation replacement, OLTC overhaul, gasket and bushing replacement, vacuum oil filling, dielectric tests, and leak/heat run verification.
一月 23, 2026 11:13 下午 回复至: What is the difference between a power and a distribution transformer? #331551Power transformers operate at transmission voltages with high utilization and are optimized for efficiency at or near full load. Distribution transformers operate at lower voltages, experience variable loading profiles and are optimized for low no-load losses and voltage regulation for end users.
Offline DGA, PD, induced voltage, and dielectric oil tests evaluate insulation health; trending detects aging, moisture ingress, and localized defects.
一月 22, 2026 9:27 下午 回复至: Where are big power transformers installed in utility transmission systems? #331337Large GSUs and transmission autotransformers are installed in HV yards, substation compounds, and generation switchyards. They connect generating units to the transmission backbone and provide voltage transformation for long-distance power transfer.
kVA rating is established from winding current and voltage limits, verified by thermal testing and impedance characteristics. Manufacturers ensure the unit can sustain rated kVA at specified ambient temperature without exceeding insulation thermal class.
Heavy industries (steel, cement, petrochem, mining, pulp & paper, data centers, and rail) deploy MV/HV transformers for distribution, motor drives, and process electrification.
一月 20, 2026 10:33 下午 回复至: Can the TOR-5 online monitoring system also display the oil breakdown voltage? #330698In general, TOR-5 does not directly measure or display oil breakdown voltage, because BDV testing requires applying a controlled high voltage between electrodes in a test cell, which cannot be done safely or reliably online. TOR-5 focuses on parameters that correlate with dielectric strength, such as moisture, temperature, and hydrogen trends. These give an indirect indication of insulation condition, but periodic offline BDV testing with a dedicated tester is still necessary for an actual breakdown voltage value.
一月 18, 2026 8:50 下午 回复至: What does a power current transformer measure in electrical systems? #330246A current transformer (CT) scales large line currents down to small, manageable values for metering and protection relays. It maintains a precise ratio and phase relationship within specified accuracy classes. CTs allow safe connection of instruments without exposing them to high primary currents. In protection applications, CT performance during faults is critical, as relays rely on accurate current reproduction to trip breakers correctly and isolate faults in the power system.
十一月 12, 2025 3:23 下午 回复至: Interested in Bitumen Emulsion Laboratory System CLM-100.1 for asphalt emulsion. #327611The CLM-100.1 laboratory plant produces up to 100 L/h of bitumen emulsion and is ideal for pilot-scale testing or R&D.
十一月 12, 2025 4:21 上午 回复至: Want to buy a bitumen filter. Pump capacity is about 60 tons per hour. #327565GlobeCore supplies high-capacity bitumen filters compatible with pumps up to 80 t/h. The system ensures continuous filtration before storage or emulsification.
十一月 11, 2025 9:39 上午 回复至: Looking for an oil purification system with capacity not less than 6000 L/h. The unit should be portable, double-chamber, high-vacuum type, mounted on a trailer, and equipped with three-step heaters. Please include warranty terms, storage instructions, catalog, and documentation. #327492The CMM-6 oil purification plant meets these parameters. It performs heating, degassing, and fine filtration of transformer oil, reaching moisture content below 10 ppm. The system is mounted on a trailer and includes a double-stage vacuum chamber. Full documentation, warranty, and certificates will be provided.
十一月 8, 2025 12:16 下午 回复至: I want to set up a new transformer oil reclamation plant. Kindly let me contact a dealer in India. #327210Thank you for your interest. GlobeCore has regional partners in India who can support installation and commissioning of transformer oil reclamation plants (CMM-R series). We will connect you with the authorized representative for your area.
The 70 L/min transformer oil purifier corresponds to a CMM-4 unit. It performs degassing and dehydration using vacuum technology. We will provide pricing and delivery details.
Please provide the unit’s serial number or production date so that we can send the correct operation manual and acceptance certificate for your CMM-0.6L oil purification unit. Documentation is issued in electronic format (PDF) and can be sent upon confirmation of model details.
It restores used oil by removing contaminants, acids, and sludge. GlobeCore’s used oil cleaning machines support closed-loop reuse, cutting costs and reducing environmental impact for industrial clients.
-