- 您需要先登录才可以创建新话题。
Chris Miller
Chris Miller
已创建论坛回复
-
作者帖子
-
Generator Step-Up (GSU) and Unit Auxiliary Transformers dominate, usually 3-phase oil-immersed OA/FA/FOA types with HV >110 kV and high MVA ratings.
A typical power station includes Generator Step-Up (GSU) transformers, Unit Auxiliary Transformers (UAT), Station Service Transformers, Excitation Transformers, and sometimes Start-Up/Black-Start transformers. Each handles different grid and plant loads.
The largest power transformers are located in extra-high voltage transmission substations, HVDC converter stations, interties between national grids, nuclear and thermal generating stations, and large renewable installations (offshore wind and utility-scale solar). Regions with ultra-high transmission (735-1100 kV) such as China, India, Russia, and Canada host the biggest units.
The design process considers service voltage, system fault levels, loading profile, efficiency targets, noise limits, and lifecycle cost. Engineers choose core materials, insulation systems, winding configurations, and cooling types to meet performance goals while complying with standards. Mechanical design must withstand short-circuit forces and shipping stresses. Accessories like OLTCs, bushings, and monitoring devices are selected based on application. Environmental constraints, including footprint, transportation limits, and required environmental performance (leak containment, fire safety), also influence the final design.
一月 24, 2026 4:06 上午 回复至: How is power in a transformer calculated under real load conditions? #331589Real power is P=VIcos? adjusted for copper, core, and stray losses; apparent power S=kVA guides rating.
Power transformers operate at transmission voltages and high kVA ratings, optimized for minimal losses at full load and long-distance transfer. Distribution transformers operate at lower voltages near end-users and are optimized for good efficiency over varying load levels. Power transformers typically serve substations between generation and transmission networks, while distribution transformers feed commercial or residential loads at utilization voltages.
Power transformers (GSU, transmission) are primarily rated in MVA with focus on high voltage, short-circuit strength, and efficiency at high load factors. Distribution transformers emphasize kVA at lower voltages, diverse loading patterns, and regulation at customer end. Test regimes, duty cycles, and design priorities differ: power transformers handle bulk transfer and higher transients, while distribution units serve many small loads, often with frequent load variation and voltage drop concerns.
一月 22, 2026 8:33 上午 回复至: How does the CMM-12R oil regeneration systems impact transformer paper insulation? #331208By circulating regenerated oil through the transformer, contaminants embedded in the paper insulation can be dislodged and captured in the unit’s sorbent, improving the condition of both oil and solid insulation simultaneously.
一月 22, 2026 2:18 上午 回复至: How does CMM-G help reduce total cost of ownership for wind turbines? #331119By enabling fast, thorough oil changes with high-quality filtration and heating, the CMM-G helps maintain optimal lubricant condition, reducing wear, avoiding premature gearbox failure, and minimizing turbine downtime. This directly lowers maintenance costs, improves energy production uptime, and reduces expensive component replacements.
一月 21, 2026 1:46 下午 回复至: How does LFD affect the duration of transformer downtime during maintenance? #330931LFD usually reduces total downtime, especially for large power transformers. Because heating is generated directly in the windings, the drying phase is much faster than in hot-air or oven methods for thick insulation. In many cases, drying time is shortened from weeks to several days, and there is no need to remove and transport the active part to an external oven. The trade-off is that setup and monitoring are more specialized, but overall outage time is typically significantly shorter and more predictable with LFD.
一月 20, 2026 6:05 下午 回复至: In which standard is the AW (water in oil activity) value mentioned? #330634The concept of water activity (aw) in transformer oil is mainly addressed in IEC 60814 and more explicitly in IEC 60422, which describes interpretation of dissolved water and moisture equilibrium between oil and paper. These standards explain the relationship between aw, relative saturation, and ppm at a given temperature. IEEE guides (such as IEEE C57.106) also reference relative saturation, but IEC documents are the primary source for formal use of water activity in diagnostics.
一月 20, 2026 3:05 下午 回复至: What is the service life of the filters in the TOR-5 online transformer monitoring system? #330591The service life of the filters in TOR-5 is not defined by calendar time alone, but mainly by the amount of moisture they actually adsorb and the number of regeneration cycles. In stable mid-life transformers, a single cartridge set can typically operate for several months before regeneration is required. With proper regeneration, the same zeolite can be reused many times, so the practical lifetime is often several years. What really limits life is oil contamination and mechanical degradation, not simple saturation.
一月 20, 2026 1:13 下午 回复至: What applications require a distribution power transformer in electrical networks? #330563Distribution transformers supply end-user voltages for commercial, residential, and industrial loads from medium-voltage feeders.
一月 20, 2026 9:31 上午 回复至: How do engineers design a power transformer for specific kVA ratings? #330500Design starts with kVA demand, voltage class, cooling method, insulation, impedance, and thermal limits. Core cross-section, flux density, conductor size, winding arrangement, and cooling ducts are calculated to meet losses, temperature rise, and efficiency targets.
一月 19, 2026 5:05 上午 回复至: How does a step down power transformer reduce high voltage for end-use equipment? #330292A step-down transformer uses a lower-turns secondary to reduce voltage while increasing current proportionally. This enables customer loads to operate at utilization voltages while upstream networks remain at efficient transmission or distribution levels.
Image received. I can inspect the photo and point out any obvious issues affecting dielectric strength/breakdown voltage testing—I’ll look for the electrode geometry and gap (2.5 mm per IEC 60156/ASTM D877), electrode cleanliness and wear, signs of corona or pitting on leads, proper sample container and liquid level, presence of vacuum/degassing equipment, temperature control, HV cable routing and shielding, grounding and safety interlocks, and whether the unit appears to be a benchtop or portable field BDV tester (model identification and calibration sticker if visible).
If you want a focused check, send a close-up of the electrode region and the instrument panel/label. Tell me which standard you’re following and whether the sample was degassed before the photo; with that I’ll give specific, actionable feedback on test readiness and any immediate safety or repeatability concerns.
GlobeCore’s TOR-80 is a solid choice for field-level transformer oil dielectric strength testing — it’s designed for high-voltage transformer oil breakdown measurements, offers a wide voltage range and automatic shutoff and logging, and is rugged enough for on-site use. For laboratory work where repeatability and sample conditioning matter more, I’d look at fully automated benchtop systems from established test-equipment makers (BAUR DPA-series, Doble lab oil testers and similar) that include vacuum degassing/filtration, temperature control, automatic ramping and statistical reporting to meet IEC 60156 / ASTM D877 / D1816 requirements.
Whatever unit you pick, confirm it explicitly supports the standards (2.5 mm electrode gap, prescribed ramp rate and the required number of breakdowns averaged), has traceable calibration and good service/support in your region, and includes safety interlocks and data logging. Also plan complementary tests (water by Karl Fischer, dissipation factor, interfacial tension) as dielectric strength alone can be misleading if samples aren’t properly conditioned or representative.
十一月 10, 2025 7:18 上午 回复至: Inquiry for replacement filters for transformer oil purification unit. #327374GlobeCore supplies replacement filters and cartridges for all CMM and UVR models. Please specify the filter dimensions or serial number, and we will provide compatible part details and pricing.
The CMM-2.2LT transformer oil purification unit processes 2.2 m³/h and performs vacuum dehydration, degassing, and filtration. We’ll provide price, specifications, and delivery schedule.
The TOR-100 tester measures breakdown voltage of transformer oil automatically according to IEC 60156. We will send a quotation including technical catalog, lead time, and certification details.
-
作者帖子