- 您需要先登录才可以创建新话题。
Sarah Davis
Sarah Davis
已创建论坛回复
-
作者帖子
-
Raises generator output voltage to transmission level (110-400 kV+).
Transformers allow voltage transformation for efficient transmission, grid interconnection, protection coordination, and safe delivery to end users. Without transformers, AC generation could not be economically transmitted over distance.
In a nuclear plant, the transformer system performs the same electrical role as in other thermal plants: GSUs step up generator output to transmission voltage, station service transformers supply turbine-island and balance-of-plant loads, and reserve transformers ensure black-start capability. Reliability requirements are stricter due to safety-critical infrastructure, so monitoring, redundancy, and seismic-rated installation standards are common.
To determine transformer power factor under load, you measure real power P in kW and apparent power S in kVA at the terminals, then compute power factor as PF = P / S. This can be done using power quality meters or three phase wattmeters with voltage and current transformers. For insulation power factor tests, a different concept is used, where the ratio of resistive to capacitive current in insulation is measured at test voltage. That diagnostic “power factor” indicates dielectric condition rather than load power factor.
As loading increases, winding resistance losses and stray flux losses scale with I², while cooling systems may reach limits, raising operating temperature and dielectric stress.
Transformer power factor measures the phase angle between voltage and current. A low PF increases current, copper losses, and thermal stress. Utilities monitor PF to optimize loading, reduce losses, and improve capacity utilization.
一月 24, 2026 7:58 上午 回复至: What qualifications are required for power transformer jobs in manufacturing and servicing? #331619Roles in transformer manufacturing and servicing typically require electrical engineering or electromechanical backgrounds, knowledge of IEC/IEEE standards, oil and dielectric diagnostics (DGA, PD, tan-delta), mechanical assembly, OLTC servicing, and commissioning workflows. Field technicians must understand safety, grounding, lockout/tagout, rigging, and substation procedures.
Oil filled transformers dominate substation use because they can handle high voltages and large power ratings with efficient cooling and strong insulation. The oil immersion allows compact winding arrangements, high dielectric strength and robust thermal performance, which are critical in grid substations that operate continuously and see fault currents and transients. With radiators, fans or pumps, oil systems support multiple cooling modes. Properly maintained oil insulation provides long service life, and industry standards, monitoring methods and repair practices are well established.
Losses include core losses (hysteresis and eddy currents), copper losses in windings, stray losses from leakage fields, and dielectric and mechanical losses. Cooling inefficiencies and OLTC friction also contribute marginally.
It lists kVA/MVA rating, voltage, vector group, impedance, cooling class, BIL, losses, accessories, dimensions, and testing requirements.
一月 22, 2026 6:24 上午 回复至: What does testing of power transformers involve during maintenance cycles? #331177It involves insulation tests, winding resistance, ratio, impedance, oil analysis, thermography, OLTC diagnostics, and functional protection checks.
一月 22, 2026 5:05 上午 回复至: What equipment is included in electrical transformers and power equipment? #331159It includes transformers, reactors, breakers, switchgear, protection relays, busbars, instrument transformers, surge arresters, and auxiliary control equipment.
Filtration at 3 µm and 25 µm removes particles that would otherwise act as abrasives within bearing and gear surfaces. Removing such contaminants prevents accelerated pitting, scuffing, and wear, helping extend gear life and reduce the frequency of expensive repairs or premature replacements.
Input is AC voltage and current at rated frequency; output is transformed AC at new voltage/current level with isolation. kVA is preserved minus losses.
Industrial plants commonly use medium-voltage distribution transformers (e.g., 5-35 kV) or autotransformers for large feeders. Dry-type units are frequent indoors; oil-filled for outdoor/large capacity.
一月 21, 2026 10:20 上午 回复至: What does an image of a power transformer show about cooling systems? #330866Images reveal radiator banks, fans, oil conservators, cooling ducts, and fin geometries. These details indicate heat dissipation capability, cooling class (ONAN/ONAF/ONAF-ODAF), and transformer rating characteristics.
一月 20, 2026 7:02 下午 回复至: What factors influence power transformer failure rates in substations? #330647Failures correlate with overloads, insulation aging, moisture, OLTC wear, bushings defects, contamination, harmonics, lightning/switching surges, and inadequate maintenance.
Distribution outages can be restored in hours by switching feeders; full replacement may take days depending on inventory and crew availability.
ABB large power transformers are deployed in transmission substations, grid interconnections, HVDC converter stations, renewable plants, industrial process facilities, and urban substations where compact footprints and advanced cooling/monitoring systems are important. Utilities use them for high reliability and standardized IEC/IEEE compliance.
GlobeCore supplies transformer oil storage and handling systems, including tanks, filtration modules, and transfer pumps. We can provide technical drawings, pricing, and delivery schedule.
-
作者帖子