What type of sensor is used in the TOR-5 online transformer monitoring system to detect hydrogen?
- 该话题包含 1个回复,2 人参与,最后由 更新于 1周、 2天前 。
Answers
-
一月 20, 2026 12:42 下午 by David Sutton
In TOR-5, hydrogen detection is typically based on an electrochemical sensor rather than optical or chromatographic methods. This type of sensor is well suited for continuous online operation because it is compact, relatively stable, and sensitive in the low ppm range that is critical for early fault detection. It does not provide full gas composition, but it reliably tracks hydrogen trends over time, which is often the earliest indicator of partial discharges or thermal degradation inside the transformer.