Are there any limitations on taking oil samples when the TOR-5 online monitoring system is connected to the transformer?
- 该话题包含 1个回复,2 人参与,最后由 更新于 1周、 2天前 。
Answers
-
一月 20, 2026 8:46 下午 by Sandra Green
In normal practice there are no strict limitations on taking oil samples while TOR-5 is connected, as long as sampling is done correctly from a dedicated sampling valve. The system is designed to work in parallel with routine diagnostics, and temporary sampling does not disturb its measurements. The main precautions are to avoid introducing air, moisture, or particles into the circuit and to ensure the flow is stabilized after sampling. Poor sampling technique can influence moisture or gas readings for some time, so flushing the valve and allowing the system to re-equilibrate is important.