GlobeCore FAQ
From what volume of oil in a transformer can the continuous online drying unit CMM-260C be connected?
- 该话题包含 1个回复,2 人参与,最后由 更新于 1周、 2天前 。
Answers
-
一月 21, 2026 6:00 上午 by Rachel Wright
In practice, CMM-260C is intended for medium and large oil volumes, not for small distribution transformers. Typical application starts from about 5-10 tons of oil and above, where continuous conditioning makes economic and technical sense. For very small oil volumes, the circulation rate would be too high relative to tank volume and control becomes difficult. The unit is mainly justified for power transformers where long-term moisture stabilization is required.