Does the TOR-5 online monitoring system eliminate the need for chromatographic gas analysis in maintenance?
- 该话题包含 1个回复,2 人参与,最后由 更新于 1周、 2天前 。
Answers
-
一月 20, 2026 9:03 下午 by William Foster
In practice, TOR-5 does not eliminate the need for chromatographic DGA, it complements it. TOR-5 continuously tracks key indicator parameters such as hydrogen, moisture, and trends, which is very effective for early fault detection and alarming. However, it does not provide full multi-gas composition (methane, ethane, ethylene, acetylene) required for fault type classification. Periodic laboratory chromatography is still necessary for root-cause analysis and condition assessment, while TOR-5 mainly reduces the risk of missing fast-developing problems between scheduled DGA tests.