enero 27, 2026 a las 9:34 pm en respuesta a: How long does it take to fix a power transformer? #332323佐々木 篤司Miembro
Distribution pole units may be changed in hours; substation GSUs may require days for inspection or months if replacement/transportation is required.
enero 25, 2026 a las 4:01 am en respuesta a: What components are inside a power transformer and how do they influence performance? #331787佐々木 篤司MiembroThe core material and geometry determine core losses, flux distribution, and efficiency. Winding design (conductor size, layout, insulation) affects copper losses, short-circuit withstand, and leakage reactance. Insulation quality influences dielectric strength, aging rate, and reliability. Cooling ducts and oil flow paths directly impact temperature rise and load capability. Tap changers enable voltage regulation but introduce contact wear and additional losses. Structural components, shields, and leads manage mechanical forces and stray fields, influencing noise, hotspots, and long-term stability.
enero 22, 2026 a las 6:48 pm en respuesta a: How are power transformers calculations performed for kVA, voltage, and current? #331317佐々木 篤司MiembrokVA = ?3 × VLL × Iline for three-phase units; single-phase uses V × I. Turns ratio defines voltage/current relationships.
enero 22, 2026 a las 10:39 am en respuesta a: How does the system improve oxidation stability of regenerated oil? #331239佐々木 篤司MiembroThrough sorbent adsorption and contaminant removal, oxidation resistance is restored, which slows future degradation and helps maintain performance under thermal and electrical stress.
enero 22, 2026 a las 6:28 am en respuesta a: How does the CMM-12R oil regeneration systems handle oil losses during processing? #331179佐々木 篤司MiembroThe system operates with controlled oil losses, typically in the 2-25% range during regeneration. Losses depend on oil condition and process parameters, which are managed by integrating vacuum and filtration control.
enero 21, 2026 a las 11:58 am en respuesta a: How does the principle of low-frequency heating work in LFD? Why is low frequency effective for drying windings? #330890佐々木 篤司MiembroLow-frequency heating works by circulating a high current at very low frequency (typically a few hertz) directly through the transformer windings. At low frequency, the inductive reactance is small, so you can drive large currents at relatively low voltage. This produces uniform I²R losses inside the copper conductors, which heat the windings from the inside outward. This is effective for drying because moisture diffusion in thick paper is slow, and internal heating creates a strong temperature and vapor pressure gradient that pushes water toward the surface, where it can be removed by vacuum. High-frequency or external heating cannot achieve this same uniform internal heating in massive windings.
enero 21, 2026 a las 3:13 am en respuesta a: What types of power transformers are used in electrical grids? #330764佐々木 篤司MiembroGSUs, transmission autotransformers, substation step-downs, distribution transformers, and station service/auxiliary units.
enero 20, 2026 a las 12:32 am en respuesta a: What industries are served by LD Power Transformers Pvt Ltd? #330432佐々木 篤司MiembroCompanies like LD Power Transformers Pvt Ltd typically serve utilities, heavy industry, infrastructure projects, renewable energy plants and large commercial facilities. Their products include distribution and power transformers for substations, industrial process plants, mining, steel mills, petrochemicals and large building complexes. They may also supply transformers for rail traction, wind and solar farms and captive power plants. Service offerings often cover repairs, upgrades and on site maintenance for these sectors across regional or export markets.
enero 19, 2026 a las 6:27 pm en respuesta a: How does load current influence power factor in a transformer? #330386佐々木 篤司MiembroAt light load, magnetizing current dominates, reducing power factor; as load increases, PF improves until copper and core losses shift phase angle.
佐々木 篤司MiembroAC supply energizes primary windings. Magnetic coupling transfers power to secondary circuits feeding downstream loads.
enero 19, 2026 a las 7:57 am en respuesta a: In what sectors are ABB power transformers used? #330308佐々木 篤司MiembroABB units serve transmission, distribution, heavy industry, mining, rail electrification, and renewable integration sectors.
enero 19, 2026 a las 4:22 am en respuesta a: What information is included in a Siemens power transformer catalogue? #330288佐々木 篤司MiembroA Siemens catalogue includes portfolio overviews, voltage classes, MVA ranges, cooling types, tap changer options, insulation systems, digital monitoring modules, standards compliance, and typical configurations for utilities and industry. It also provides dimensional data, transport weights, loss classes, environmental options (bio based oils, ester fluids), and service offerings such as refurbishment and field testing. Catalogues help planners select suitable models for substation upgrades and new builds.
noviembre 12, 2025 a las 3:06 pm en respuesta a: Looking for a bare-shaft colloid mill for emulsion production. #327609佐々木 篤司MiembroThe CLM-4.1 bare-shaft mill is suitable for integration into existing plants. It provides precise emulsification for 3-6 t/h throughput.
noviembre 8, 2025 a las 9:07 am en respuesta a: I’m looking for this kind of oil-treatment plants? (specification ? 6000 L/h, IEC 60422, ? 2 µm filtration, 480 V / 220 V 60 Hz, ? 10 ppm final moisture) #327198佐々木 篤司MiembroThe CMM-6RL regeneration plant fully meets these specifications. It processes up to 6000 L/h, includes heating, degassing, dehumidifying, and filtration (< 2 µm) modules, with automatic flow and safety control. It operates on 480 V or 220 V 60 Hz power and achieves residual moisture ? 10 ppm after a single pass. A detailed quotation and compliance statement to IEC 60422 can be provided.
septiembre 10, 2025 a las 1:19 pm en respuesta a: What is the transformer BDV test and what does it reveal? #325227佐々木 篤司MiembroIt tests the oil’s dielectric strength. Low BDV indicates aging or contaminated oil. GlobeCore equipment is used worldwide to restore BDV levels through advanced vacuum and filtration technology, helping avoid outages.
septiembre 10, 2025 a las 7:30 am en respuesta a: RE: What is an oil BDV tester and how accurate is it? #325078佐々木 篤司MiembroA quality transformer oil purifier machine should offer vacuum degassing, moisture removal to <10 ppm, and filtration to 1 �m. GlobeCore's models also include built-in BDV testing, flow control, and IEC compliance. They're suitable for both on-site and depot maintenance.
septiembre 9, 2025 a las 11:43 am en respuesta a: What is transformer oil reconditioning and how is it different from purification? #324925佐々木 篤司MiembroReconditioning includes deep adsorption treatment to restore oil properties, not just remove particles or moisture. GlobeCore’s CMM-R units recondition oil onsite – making old oil usable again per IEC 60422.
agosto 5, 2025 a las 4:50 pm en respuesta a: What is Shell Turbine Oil 68 and how is it serviced? #323986佐々木 篤司MiembroShell Turbine Oil 68 is designed for heavy-duty industrial turbines where thicker lubrication is needed. GlobeCore treatment units filter and degas Shell 68, extending its operational stability.
agosto 3, 2025 a las 12:06 am en respuesta a: Transformer oil kaise banta hai? (How is transformer oil made?) #323572佐々木 篤司MiembroTransformer oil is produced by refining and purifying mineral base stocks, or by synthesizing esters and silicone fluids for specialized applications. GlobeCore systems ensure the oil meets IEC and IEEE standards by removing moisture, gases, and impurities.
佐々木 篤司MiembroTransformer oil is a specialized dielectric liquid that serves as a coolant and insulator for power and distribution transformers. GlobeCore equipment processes these oils to maintain dielectric strength and thermal efficiency.
-