A standard diesel purification unit can easily clean dyed diesel fuel by removing water and solid contaminants, but it will not remove the dye itself. The dye is a fully dissolved chemical component of the fuel and cannot be separated by filtration or vacuum treatment. To actually remove the color, special adsorption or chemical processes would be required, which are outside the scope of normal fuel cleaning equipment.
enero 28, 2026 a las 5:17 am en respuesta a: How to calculate power rating of a transformer? #332381Brandon MartinMiembroS (kVA/MVA) = V × I (1?) or ?3 × V × I (3?) at rated temperature and cooling class.
enero 27, 2026 a las 1:36 pm en respuesta a: What does a step down transformer on a power line near your home do? #332258Brandon MartinMiembroIt reduces medium-voltage distribution feeders to residential low voltage for safe utilization.
enero 26, 2026 a las 8:38 pm en respuesta a: what is the significance of vector grouping in power transformers? #332115Brandon MartinMiembroVector grouping indicates the relative phase displacement and winding connections of a three phase transformer, for example Dyn11 or YNd1. This information is vital when paralleling transformers, designing protection, and analyzing fault currents. Different vector groups produce different phase shifts between primary and secondary, which can cause circulating currents or misoperation of relays if mismatched. Engineers use vector groups to ensure compatibility with existing network phasing, motor connections and grounding schemes. The designation also helps interpret test results and diagnose issues like unbalance or unexpected zero sequence behavior.
enero 26, 2026 a las 8:22 pm en respuesta a: which of the following is a type of transformer power distribution bank? #332113Brandon MartinMiembroIn distribution systems, common transformer bank types include three single phase transformers connected as a three phase bank, often in delta delta, delta wye or wye delta configurations, and single three phase distribution transformers with all windings on one core. Other bank configurations involve open delta for emergency or reduced capacity operation, and special arrangements like Scott connections for two phase to three phase conversion. When someone asks this question, they usually want to distinguish between three single phase units in a bank and one integrated three phase transformer.
enero 26, 2026 a las 11:53 am en respuesta a: Why is a CT mounted in a power transformer bushing? #332029Brandon MartinMiembroBushing CTs provide current measurements for differential protection, metering, and fault detection. Mounting CTs internally improves accuracy and saves space at substations.
enero 26, 2026 a las 11:38 am en respuesta a: Why does the difference between a distribution transformer and a power transformer matter in grid design? #332027Brandon MartinMiembroDistribution transformers emphasize voltage regulation at LV/MV and are optimized for variable load profiles. Power transformers handle HV/EHV levels, bulk transfer, and grid stability. Grid design relies on proper segmentation for protection, tap control, and redundancy.
enero 25, 2026 a las 3:30 am en respuesta a: What procedures are used in testing of power transformers? #331783Brandon MartinMiembroTesting combines dielectric, thermal, mechanical, OLTC, and oil tests to certify compliance and reliability.
enero 24, 2026 a las 4:58 pm en respuesta a: How is power transformer size determined for load and kVA? #331701Brandon MartinMiembroSizing considers peak kVA, PF, ambient temperature, cooling class, and contingency capacity.
enero 24, 2026 a las 2:54 pm en respuesta a: What failures lead to destruction of industrial power transformers? #331685Brandon MartinMiembroShort-circuit forces, insulation collapse, overheating, bushing flashover, OLTC arcing, and oil degradation can cause catastrophic failures if undetected.
enero 23, 2026 a las 1:43 pm en respuesta a: What does percentage impedance of a power transformer indicate? #331459Brandon MartinMiembroPercentage impedance indicates voltage drop under full-load current and defines the transformer’s short-circuit current capability. It is crucial for fault studies, protection coordination, and parallel operation.
enero 22, 2026 a las 10:06 am en respuesta a: What does Hyundai Power Transformer in Montgomery, AL produce? #331231Brandon MartinMiembroIt produces medium and large power transformers for utility transmission and distribution networks, supporting substation expansions, grid modernization, and export markets. Facilities typically provide design, manufacturing, testing, and refurbishment capability.
enero 22, 2026 a las 5:37 am en respuesta a: What does an insulation resistance test indicate on a power transformer? #331166Brandon MartinMiembroIt indicates the integrity of insulation between windings and core/ground. Using megohm measurements at defined test voltages, the test detects moisture, carbon tracking, or breakdown paths. Insulation resistance trending helps identify aging before critical failure and is common during commissioning, outages, and post-fault diagnostics.
enero 22, 2026 a las 4:41 am en respuesta a: How does the TSS improve operational efficiency during oil purification tasks? #331153Brandon MartinMiembroBy enabling secure connection of oil filtration, degassing, and drying equipment, the TSS allows operators to perform continuous oil-quality improvement without unnecessary stoppages. Automatic shutdown mechanisms reduce downtime due to safety events and improve efficiency during lengthy oil treatment operations.
enero 21, 2026 a las 9:31 pm en respuesta a: How does the unit handle the removal of used oil from the gearbox? #331051Brandon MartinMiembroIn the «old oil drain» mode, the CMM-G uses a vacuum pump to extract used lubricant from the wind turbine gearbox into the onboard waste oil tank. This vacuum extraction ensures that oil is removed efficiently from all accessible cavities and passages, reducing the risk of leaving degraded oil behind, which could otherwise contribute to increased wear or contamination after a new oil fill.
enero 21, 2026 a las 9:13 pm en respuesta a: What are the three main operating modes of the CMM-G unit during an oil change? #331047Brandon MartinMiembroThe three main operational modes of the CMM-G are: (1) draining the used oil using a vacuum pump, (2) gearbox flushing where high-pressure flushing fluid is forced through internal channels to remove residual contaminants, and (3) supplying clean heated and filtered oil back into the gearbox. Each mode is essential to ensure contaminants are removed and fresh oil meets required cleanliness levels before turbine operation resumes.
enero 21, 2026 a las 2:57 pm en respuesta a: What safety measures are ????????????? in the LFD device to prevent overheating of the windings or other malfunctions? #330949Brandon MartinMiembroModern LFD units include several built-in safety layers to prevent overheating and abnormal operation. The most important are multiple independent temperature sensors installed on different windings and structural parts, with automatic power reduction or shutdown if any limit is exceeded. Current and voltage are continuously monitored to avoid overcurrent conditions. In addition, there are software interlocks, emergency stop circuits, and alarms for loss of vacuum or cooling. These protections ensure that heating remains uniform and that any abnormal trend is detected early before it can damage the insulation.
enero 21, 2026 a las 11:22 am en respuesta a: Is it necessary to disconnect the TOR-5 system from the transformer in order to replace the filters? #330880Brandon MartinMiembroIn normal practice, it is not necessary to disconnect TOR-5 from the transformer when replacing the filters, provided the system is designed with proper isolation valves. The circulation loop can be shut off locally, the filter housing depressurized and opened, and the cartridge replaced while the transformer remains in service. This is an important feature for online systems, because it avoids disturbing operation and losing trend continuity. Only in very simple installations without bypass or isolation would a full disconnection be required.
enero 21, 2026 a las 2:08 am en respuesta a: If a vacuum system is added to the TOR-5 online transformer monitoring system, is it possible to perform degassing? #330748Brandon MartinMiembroYes, adding a vacuum module makes real degassing technically possible, but with important limitations. In that configuration, TOR-5 no longer works only as a conditioner, but as a low-capacity online degasser: oil is circulated through a small vacuum chamber where dissolved gases are released. This is effective for gradual hydrogen and air removal during long-term operation. However, it cannot replace a full-scale vacuum oil processing unit for fast deep degassing after major faults or oil filling. It is a stabilization tool, not an emergency treatment system.
Brandon MartinMiembroCore assembly, winding fabrication, insulation placement, tanking, oil processing, vacuum filling, and factory testing complete the build.
-