What are the acetylene limits in transformer oil?
- Ce sujet contient 1 réponse, 2 participants et a été mis à jour pour la dernière fois par , le il y a 1 année et 3 mois.
Answers
-
août 26, 2024 à 12:15 pm by Laura Anderson
Ideally, there should be no detectable acetylene in transformer oil under normal operating conditions. Even a small amount of acetylene (greater than 0.5 parts per million or ppm) can be a cause for concern and may indicate arcing within the transformer. If acetylene is detected, it typically triggers a more detailed investigation through Dissolved Gas Analysis (DGA) to determine the extent of the fault and the necessary corrective actions.