TOR-2 Hydrogen and Moisture Analyzer for Transformer Oil Monitoring
Moisture content | Hydrogen content | Compact | Small footprint
The TOR-2 transformer oil express-tester is designed to determine the moisture and hydrogen content in mineral transformer oils. Moisture and hydrogen content is measured in parts per million (ppm).
Knowing the content of hydrogen and moisture in the oil, as well as the rate of parameter change, it is possible to detect problems developing in the transformer in advance and to take timely measures to prevent damage to the transformer.
Moisture measurement
The device measures the activity of the water using a capacitance sensor, which ensures stability over time and contamination resistance. The oil temperature is also measured. The moisture content is calculated from these measurements.
Hydrogen measurement
A highly selective solid state sensor immersed directly in oil is used to measure hydrogen content. The sensor ensures accuracy and reliability of direct measurements. Low solubility of hydrogen in oil and its high diffusion capacity make it easier to detect at low concentrations, so a problem in the transformer can be identified early.
| No. |
Parameter |
Value |
| Moisture measurement | ||
| 1 | Operating range for active water, aw |
0…1 |
| 2 | Accuracy at 20 °C (68 °F) |
±0.02 aw (0…0.9 aw) ±0.03 aw (0.9…1 aw) |
| 3 | Temperature measurement |
Yes |
| 4 | Oil temperature, °С (°F) |
0…55 (32… 131) |
| Hydrogen measurement | ||
| 6 | Range, ppm |
25–5,000 |
| 7 | Accuracy |
20 % of readings, or 25 ppm |
| 8 | Repeatability |
10 % of readings, or 15 ppm |
| 9 | Response time |
<60 min (90 % step change) |
| 10 | Cross-sensitivity: |
Below 2% cross-sensitivity to other gases (CO, CO2, hydrocarbons) |
| 11 | Oil temperature, °С (°F) |
0…55 (32… 131) |
| 13 | Power, W |
60 |
| 14 | 50 Hz AC power supply voltage, V |
220 |
| 15 | Dimensions, mm (in)
— length — width — height |
190 (7.5) 255 (10) 365 (14.4) |
| 16 | Weight, kg (lbs), max |
5.5 (12) |
- Detection of moisture and hydrogen even in small quantities.
- Continuous monitoring of hydrogen content provides reliable information on incipient damage that can lead to transformer failure.
- Small size.
- Easy operation (in order to change the oil sample, simply replace the removable intake container and press the Start button to begin the measurement).
- No consumables required for measurements.
- The presence of other gases in the oil does not affect the reliability of measurements.
- Easy calibration.
- Maintenance-free.
What is the difference between dissolved gas analysis (DGA) and the method used in the TOR-2 instrument?
GlobeCore’s approach is to use the concentration and rate of change of a single key gas-hydrogen-for diagnostics, rather than the concentrations of seven gases, as in most existing methods. Hydrogen was selected because it is one of the first gases to form as transformer faults develop. Hydrogen accounts for 59.1% of all gases generated during the decomposition of oil molecules.
The diagnostic information is supplemented by measuring the water content in the oil. Water is produced during the decomposition of cellulose molecules, and elevated water content may indicate developing faults in the transformer’s solid insulation.
By monitoring hydrogen and water content, as well as the rate of change in hydrogen concentration, substation operators can be alerted to potentially developing transformer faults. This allows them to adjust the maintenance schedule and prevent transformer failure.
Can TOR-2 be used to identify the type of transformer fault?
No. TOR-2 provides a quick indication of whether a fault may be developing in the transformer. More in-depth testing and calculations are required to identify the specific type of fault.
Does the TOR-2 instrument require calibration?
The moisture sensor is calibrated at the manufacturer’s factory and does not require any additional calibration. The hydrogen sensor automatically self-calibrates every 12 hours according to the internal real-time clock.
Which is more important for transformer diagnostics - hydrogen concentration or the rate of change in hydrogen concentration?
Both parameters are important.
Can TOR-2 be used to diagnose other oil-filled electrical equipment besides power transformers?
Yes.