СММur-1L mobile oil plant

The СММur-1L continues the excellent functionality of this series of equipment, but is designed to be more compact and economical.

The СММur-1L purifies electrical insulation oil1Insulating oil is an oil that is stable at high temperatures and has excellent electrical insulating properties. with viscosity2The viscosity of a fluid is a measure of its resistance to deformation at a given rate. below 70 cSt at 50o, removing water and particulate matter.

This device can heat oil-filled electrical equipment with hot transformer oil and evacuate air from vacuum3Vacuum is space devoid of matter. An approximation to such vacuum is a region with a gaseous pressure much less than atmospheric pressure. systems.

The unit ensures oil purification4Oil purification removes oil contaminants in order to prolong oil service life. according to class -/14/12 from initial class -/18/16 (contaminant content by weight less than 0.004%) after multiple passes of the product through the filters5Filter is a device which separates solids from fluids (liquids or gases) by adding a medium through which only the fluid can pass..

The СММur-1L is used in the course of commissioning, repairs and operation of oil-filled high voltage systems (power transformers6A transformer is a static electrical device that transfers electrical energy between two or more circuits., high voltage switches7Switchgear is composed of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. etc).

Parameter

Value

1 Processing rate, m3/hour:

1.0

2 Max oil output temperature in heating mode, °С

60

  3* Processed oil parameters (initial moisture less than 100 ppm):

– filtration, μm

– minimum dielectric strength, kV

– ISO 4406 purity class

 

 

5

75

-/14/12

4 Output height relative to the outlet, meters

20

5 Max input pressure, MPa

0,1

6 Max output pressure, MPa

0,25

7 Oil heater power, kW

20,4

8 Mean heater surface power, W/cm2, max  

1,1

9 Nominal power, kW

25

10 Three phase AC power (voltage, frequency)

Custom

11 Max dimensions, mm

– length

– width

– height

 

1500

1000

1255

12 Weight, kg, max

635

Note: * Initial oil parameters:

  • moisture below 0.005% (50 ppm);
  • oil heated to +60±5ºС for 30 minutes;
  • gas content below 10%.

  • compact size. The unit can be carried by various vehicles (ground, sea, air);
  • simple operation and maintenance;
  • increase of dielectric strength from 15 to 75 kV in several passes;
  • optimized heater design with increased heating rate without excessive power requirements;
  • sight glass of sufficient size for simple visual monitoring of oil processing.

    GlobeCore

    Leave your request

    Relative Equipment

    Support

      Introduce yourself

      logo
      Online consultant
      Ask your question
      manager
      Hello it's Anna.
      Are you interested in getting a job?
      Yes?
      Would you like to take a course on how equipment works?
      Yes?

        Add your CV.

          Introduce yourself
          Oil
          Bitumen
          Blending
          WindMill
          AVS