Call back now


    CMM-1/1 mobile oil plant

    The CMM-1/1 continues the excellent functionality of this series of equipment, but is designed to be more compact and economical.

    The CMM-1/1 purifies electrical insulation oil1Insulating oil is an oil that is stable at high temperatures and has excellent electrical insulating properties. with viscosity2The viscosity of a fluid is a measure of its resistance to deformation at a given rate. below 70 cSt at 50o, removing water and particulate matter.

    This device can heat oil-filled electrical equipment with hot transformer oil and evacuate air from vacuum3Vacuum is space devoid of matter. An approximation to such vacuum is a region with a gaseous pressure much less than atmospheric pressure. systems.

    The unit ensures oil purification4Oil purification removes oil contaminants in order to prolong oil service life. according to class -/14/12 from initial class -/18/16 (contaminant content by weight less than 0.004%) after multiple passes of the product through the filters5Filter is a device which separates solids from fluids (liquids or gases) by adding a medium through which only the fluid can pass..

    The CMM-1/1 is used in the course of commissioning, repairs and operation of oil-filled high voltage systems (power transformers6A transformer is a static electrical device that transfers electrical energy between two or more circuits., high voltage switches7Switchgear is composed of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. etc).

    Parameter

    Value

    1 Processing rate, m3/hour:

    1.0

    2 Max oil output temperature in heating mode, °С

    55

      3* Processed oil parameters (initial moisture less than 100 ppm):

    – filtration, μm

    – minimum dielectric strength, kV

    – ISO 4406 purity class

     

     

    5

    75

    -/14/12

    4 Output height relative to the outlet, meters

    20

    5 Max input pressure, MPa

    0,1

    6 Max output pressure, MPa

    0,25

    7 Oil heater power, kW

    20,4

    8 Mean heater surface power, W/cm2, max  

    1,1

    9 Nominal power, kW

    25

    10 Three phase AC power (voltage, frequency)

    Custom

    11 Max dimensions, mm

    – length

    – width

    – height

     

    1260

    1010

    1295

    12 Weight, kg, max

    500

    Note: * Initial oil parameters:

    • moisture below 0.005% (100 ppm);
    • oil heated to +60±5ºС for 30 minutes;
    • gas content below 10%.

    • compact size. The unit can be carried by various vehicles (ground, sea, air);
    • simple operation and maintenance;
    • increase of dielectric strength from 15 to 75 kV in several passes;
    • optimized heater design with increased heating rate without excessive power requirements;
    • sight glass of sufficient size for simple visual monitoring of oil processing.