CMM-12R Oil Regeneration System (With Activated Bauxite)
Cap: 1000-2000 LPH | Regeneration | Sorbent Reactivation | Economy
- Description
- Specification
- Advantages
- Application
- FAQ
- Configurator
- Payback Period
- Gallery
- Publications
The CMM-12R unit is designed for the regeneration of transformer oil by passing it through layers of a special sorbent – activated bauxite.
During the regeneration process, oil degradation products and acidic compounds are removed, and the oil becomes clean and transparent.
The GlobeCore oil regeneration process restores used oil to a condition close to that of new oil. This process makes it possible to fill transformers with oil that would otherwise have to be disposed of. Such oil can be used in the transformer for its entire service life without replacement.
| No. |
Parameter |
Value |
| 1 | Nominal capacity, L/h (gal/min) |
1,000-2,000 (4.4-8.8) |
| 2 | Oil losses during operation, % |
2-25 |
| 3 | Maximum allowable oil temperature, °C (°F) |
90 (194) |
| 4 | Outlet pressure, bar (psi) |
2.5 (36.3) |
| 5 | Maximum power consumption, kW |
55 |
| 6 | Nominal vacuum suction rate, L/h (gal/min) |
280,000 (1,232.8) |
| 7 | Activated bauxite load, kg (lbs) |
1,600 (3,527.4) |
| 8 | Power supply parameters | |
| – voltage, V |
Customizable |
|
| – frequency, Hz | ||
| 9 | Coarse filtration degree (mesh filter), µm |
100 |
| 10 | Pre-filtration degree, µm |
25 |
| 11 | Fine filtration degree, µm |
5 |
| 12 | Dimensions, mm (in) | |
| – length |
5,500 (216.5) |
|
| – width |
2,320 (91.3) |
|
| – height |
2,450 (96.5) |
|
| 13 | Weight, kg (lbs) |
6,000 (13,227) |
- Complete reclamation of waste transformer oils to a condition close to new.
- Possibility of use with degassing units.
- Possibility of reactivating the sorbent (activates bauxite) up to 300.
- Money saving due to reclaiming and reusing the oil in transformers.
Application:
Is there a difference between oil purification and oil regeneration?
The terms “purification” and “regeneration” are sometimes used interchangeably, although they actually refer to different processes. Oil regeneration is a technological process that involves the selective removal of aging products and contaminants from oil, followed by stabilization with additives to restore its quality and make it suitable for reuse in its original application.
What is the main difference between CMM-RL and CMM-R units?
CMM-RL units are manually operated, while CMM-R units operate automatically. In addition, the columns of CMM-RL units contain less sorbent than those of CMM-R units.
How often should transformer oil be regenerated?
There is no strictly defined interval for oil regeneration. The frequency depends on the results of oil analysis and the transformer’s operating conditions. As a general guideline, oil regeneration is performed approximately every 10-15 years.
What is the consumption rate of the regeneration sorbent in CMM-R units?
On average, 1 kg of sorbent regenerates 4 liters of oil with an acid number of 0.25 mg KOH/g.
How is sludge removed from transformer windings?
Sludge removal from transformer windings is carried out by circulating oil heated above its aniline point through the transformer. The aniline point is the temperature at which sludge begins to dissolve in the oil. This temperature is typically around 80°C. Sludge removal takes place simultaneously with oil regeneration. Only fresh or regenerated oil should be used for sludge removal.
Transformer windings can be cleaned with the transformer either energized or de-energized. The cleaning process requires 30 to 60 passes through the regeneration unit. When the transformer is de-energized, sludge dissolution becomes less effective due to the absence of winding vibrations, so the cleaning process takes longer.
Are there any sorbent losses during reactivation?
In CMM-R units, sorbent reactivation takes place directly inside the columns, eliminating the losses that could otherwise occur during unloading and loading operations.
What percentage of oil is lost during the sorbent reactivation process?
Generally, between 2% and 20%. The exact percentage depends on the initial quality of the oil.
Can oil regeneration be performed using a CMM-12R unit while the transformer is in operation?
Yes.
How to Restore the Properties of Aged Transformer Oil
Transformer Oil Processing Solutions by GlobeCore