GlobeCore / Application / Transformer oil moisture and particles content tester TOR-6

Transformer oil moisture and particles content tester TOR-6

Transformer oil moisture and particles content tester TOR-6

The TOR-6 transformer oil moisture and particles content tester, manufactured by GlobeCore, is designed to monitor the condition of the insulating fluid directly at the point of equipment operation. Transformer oil fulfils dual functions, namely insulating and cooling, thus rendering its purity and moisture content critical for the reliable operation of transformers. The TOR-6 allows you to quickly determine the moisture level (in percent or parts per million (ppm)) and the amount of mechanical impurities in accordance with international standards (e.g. ISO 4406). An increased water or particle content in transformer oil may indicate insulation wear, moisture penetration or the onset of degradation processes. The device is easy to use and has a compact design and user-friendly interface. All measurement results are displayed digitally, and the data can be saved or transferred for further analysis. The TOR-6 is suitable for laboratory work and field conditions. This meter enables you to detect deviations in the composition of transformer oil promptly, enabling you to decide whether to filter or replace it, thereby reducing the risk of accidents and extending the service life of electrical equipment.

Transformer oil moisture and particles content tester TOR-6 Specifications

No. Parameter Value
Moisture measurement characteristics
1 Operating range, aw (active water) 0…1
 2 Precision at 20 °C ±10 % or ±10 ppm
3 Temperature measurement Yes
Purity or contamination level characteristics
4 Permissible viscosity range, mm²/sec 1 to 1,000
5 Standards maintained in determining the purity class ISO 99 (ISO 4406:1999)

SAE (SAE AS 4059) or

ISO 87 (ISO 4406:1987)

NAS (NAS 1638)

6 Measuring range Measuring from ISO 9/8/7 (min) to ISO 25/24/23 (max)

Calibrated within the ISO range from 13/11/10 to 23/21/18

7 Precision ISO class ± 1/2 in calibrated range
8 Required power, W 3
9 Single phase 50 Hz AC power supply voltage, V 220
10 Dimensions, mm, not more than

– length

– width

– height

 

235

275

370

11 Weight, kg, not more than 10