×
  • You must be logged in to create new topics.

山田 英樹

山田 英樹

Forum Replies Created

Viewing 20 posts - 1 through 20 (of 74 total)
  • Author
    Posts
  • You’re correct — progressive multi-stage treatment is a key reason modern systems consistently restore and maintain diesel cleanliness. In practice you run coarse filtration first to knock out sludge, sand and large particulates (protecting downstream elements), follow with coalescing/water-separation to remove free and emulsified moisture, and finish with fine filtration/adsorptive polishing to strip dissolved contaminants, aromatics and resinous compounds that foul injectors and fuel pumps. Centrifugal separators are often integrated where rapid phase separation is needed, and automated monitoring of pressure differential and water content keeps the process reliable during long storage periods.

    Many industrial installations use modular chains that combine those exact stages: a coarse filter, a coalescing/water-removal module that can handle heavily watered fuel, and an adsorptive polishing unit with multiple adsorbent columns to restore appearance and combustion properties. Systems designed this way typically achieve stable fuel quality even from degraded feedstock, but throughput and run lengths depend on feed contamination levels. For best results, monitor ΔP across filters, track water content, and schedule adsorbent reactivation or replacement per operating hours and sensor alarms to keep the purification chain performing optimally.

    For potassium humate production I recommend using the GlobeCore AVS vortex layer device instead of a colloid mill. AVS intensifies alkaline extraction of humic substances by activating particles in an electromagnetic vortex layer, which significantly increases yield and reduces processing time. It does not use a rotor-stator gap; process control is achieved by the electromagnetic field and working elements. A typical line is: mixing tank (raw material + KOH) ? AVS (inline or recirculation) ? solid separation ? fine filtration. AVS-100 or AVS-150 can be selected depending on the required capacity.

    Efficiency peaks near unity PF in normal grid operation because copper losses decrease with reduced reactive current.

    in reply to: what are power transformers used for? #332175

    Power transformers are used to transfer large amounts of electrical energy between circuits at different voltage levels in power systems. They step up generator output to transmission voltages, interconnect transmission networks, and step down voltage at substations for distribution and industrial loads. They provide galvanic isolation between sections of the grid, help manage losses by enabling high voltage transmission, and support voltage regulation via tap changers. In industrial plants, power transformers feed major motors, drives and process systems, forming the backbone of electrical supply infrastructure.

    in reply to: Why does a power pole transformer buzz during operation? #332015

    The audible hum is caused by magnetostriction in the steel core laminations and mechanical vibration at twice the grid frequency. Aging, loose components, or load changes can increase noise levels.

    Utilities source transformers via OEMs, EPC firms, integrators, and tender platforms with IEC/IEEE compliance. Procurement often requires FAT/SAT, logistics planning, and warranty terms.

    Power plants run near continuous rated load. High efficiency minimizes thermal losses and reduces cooling demand. Large units must withstand fault currents, switching transients, and grid disturbances without insulation degradation.

    kVA=S=V×I for each winding; 3-phase uses ?3×V×I. Ratings include thermal and impedance margins.

    Installation must address foundation strength, lifting and handling methods, clearances, grounding, and routing of high-voltage connections. Oil filling and vacuum treatment are done under controlled conditions. Cooling, ventilation, and access for maintenance must be planned. Protection and control wiring, CT/VT connections, and communication links must be properly terminated and tested. Environmental factors such as flood risk, lightning exposure, and fire barriers are accounted for. Finally, commissioning tests verify installation integrity before energization.

    In a power station the transformer is the interface between the generator bus and the transmission grid. After mechanical energy is converted to electrical power by the generator, the step up transformer converts this power to a higher voltage that is suitable for efficient transmission. Additional station service transformers supply auxiliary loads within the plant. Together they ensure energy flows from the generator into the grid with acceptable losses, proper voltage control and safe isolation between different system parts.

    Commissioning typically includes visual inspection, nameplate verification, oil level and moisture checks, ratio test, winding resistance test, insulation resistance, tan-delta, DGA baseline sampling, OLTC functional checks, bushing inspection, cooling system tests, relay and protection coordination, tap verification, vector group confirmation, and energization under controlled conditions. Load acceptance and thermal stability are confirmed before handover.

    A typical substation picture shows the transformer tank, radiators, HV/LV bushings, and connections to busbars or overhead lines. You often see surge arresters, CTs, and VT units nearby, along with OLTC cabinets and cable boxes. Oil conservators, nitrogen systems, and fire barriers may also be visible. The layout illustrates clearances, grounding, and access for maintenance, providing a visual context for how the transformer fits into the substation’s overall electrical and physical design.

    For high-voltage transformer oil dielectric strength testing pick a bench or portable BDV tester that explicitly complies with IEC 60156, offers an automatic, adjustable HV ramp and rapid discharge, supports the standard 2.5 mm electrode geometry, and includes data logging and calibration traceability. GlobeCore’s TOR-80 is a solid option many operators use in the field; other well‑established manufacturers in this space are BAUR and Megger, which produce robust BDV testers and service/calibration support for transformer oil breakdown voltage measurement.

    Practical performance comes from correct sample preparation and instrument features as much as raw HV capability: vacuum dehydration/degassing, temperature control, clean electrodes, safety interlocks and an easy-to-follow IEC 60156 test routine make results repeatable and defensible. Always run the prescribed sequence of breakdown measurements and report the mean per the standard, verify operation with a calibration oil and scheduled calibration, and choose a unit with integrated vacuum pump/data export if you test oil on-site frequently.

    The USB-3 laboratory unit allows small-batch polymer modification of bitumen up to 20 L/h. It includes a heating tank, dosing pump, and miniature colloid mill.

    The CMM-0.6L transformer oil purification unit has a capacity of 600 L/h and removes water, gases, and solid contaminants. Standard lead time is 4-6 weeks. We will send pricing and shipping details to Monterrey, Mexico.

    in reply to: Interested in the oil regeneration machine. Price. #327162

    GlobeCore offers oil regeneration systems (CMM-R series) that restore aged transformer oil by removing acids and oxidation products. Please specify required capacity (e.g., 2, 4, 6 or 10 m³/h) for pricing and technical details.

    Thank you for your interest. Please specify which model of transformer oil testing equipment you require (e.g., TOR-1, TOR-80, or TOR-100). We will prepare a quotation including shipping options to Nigeria.

    GlobeCore provides combined filtration and vacuuming units for transformer servicing. Systems include oil heating, degassing, and vacuum evacuation features. We will prepare a budgetary offer based on required flow rate and operation conditions.

    A bitumen emulsifier is a chemical agent that allows bitumen to mix with water. In GlobeCore systems, emulsifiers are automatically dosed and blended in dedicated tanks before entering the colloid mill. This guarantees consistent emulsion quality and long shelf life.

    in reply to: What is Turbine Oil 100 and where is it applied? #324026

    Turbine Oil 100 is a high-viscosity mineral lubricant used in large steam and gas turbines. GlobeCore regeneration units process Turbine Oil 100, maintaining its stability under heavy loads.

Viewing 20 posts - 1 through 20 (of 74 total)

Sign up

Sign in

To continue log in with Google.