GlobeCore / Products / Instruments - Transformer Oil Testers / TOR-8 tester for residual gas content of insulating oil

TOR-8 tester for residual gas content of insulating oil

Transformer oil analysis
The TOR-8 tester is used to measure dissolved gases in insulating oils during the degassing process in degassing machines. Its main purpose is to accurately evaluate the efficiency of gas removal from transformer oil, allowing professionals to monitor the degassing rate and ensure proper oil treatment. The measurement process takes up to 10 minutes, and the device includes an integrated thermal printer for printing results. The TOR-8 is widely used by companies involved in installation, repair, and operation of transformer oil systems, making it an essential tool for maintaining and servicing transformer equipment.
Request Price

Transformer oil degassing is necessary for removal of dissolved gases which improves the insulating properties of oil, as well as prevents corrosion and wear of power-generating equipment. TOR-8 instrument is used in the processes of removing dissolved gasses from insulating oils (oil degassing) in degassing machines. Its main purpose is to facilitate measuring the efficiency of the degassing procedures performed by these machines. The use of this instrument makes it possible to accurately evaluate the gas removal rate for oil.

The instrument is widely used at installation, repair, and operation entities dealing with transformer oil processing. Owing to this instrument, professionals can easily and efficiently monitor the degassing process, which makes up an important part in maintenance and operation of transformer equipment.

Principle of operation

The principle of the instrument’s operation is based on recording a change in gas pressure inside a cylinder under vacuum when it is filled with a portion of oil. Knowing the volumes of the cylinder and the oil filled, the pressure values inside the cylinder before and after filling, it is possible to determine the volumetric gas content.

The residual gas content is measured during operation of the degassing machine.

No. Parameter

Value

1 Measuring cell volume, L

1.2

2 Oil sample volume, L

0.5 – 0.7

3 Maximum pressure inside the instrument, Pa

0.3

4 Maximum leakage inside the instrument, Pa

26

5 Input pressure of oil, bar

0.3 – 10

6 Temperature of tested oil, ºС

20 — 90

7 Maximum power requirement, kW, not more than

1

 

 

 

8

Power supply parameters

(in standard form; otherwise — upon request):

 

●       voltage, V

●       AC frequency, Hz

 

 

230

50

9 Overall dimensions, mm, not more than

— length

— height

— width

 

330

300

275

10

Weight, kg, not more than

25

  • accurate measurement of residual gas content of transformer oil;
  • reliable operation;
  • convenient and robust housing;
  • the measuring process takes up to 10 minutes;
  • the possibility to print the results using an integrated thermal printer.

Mineral transformer oil universal tester TOR-7

Mineral transformer oil universal tester TOR-7

The TOR-7 mineral transformer oil universal tester made by GlobeCore is designed to check the quality of dielectric fluids used in transformers, reactors, circuit breakers and other electrical equipment. The... Read More
Silicone transformer oil universal tester TOR-7

Silicone transformer oil universal tester TOR-7

The TOR-7 silicone transformer oil universal tester made by GlobeCore is designed to test the main characteristics of dielectric liquids, including silicone oils used in transformers, circuit breakers and other... Read More
Midel 7131 transformer oil universal tester TOR-7

Midel 7131 transformer oil universal tester TOR-7

The Midel 7131 transformer oil universal tester TOR-7, made by GlobeCore, is designed to check the main quality indicators of insulating fluid used in transformers, reactors and other high-voltage equipment.... Read More
FR3 dielectric fluid universal tester TOR-7

FR3 dielectric fluid universal tester TOR-7

The FR3 dielectric fluid universal tester TOR-7 , made by GlobeCore, is used to check the main parameters of insulating fluids used in transformers, switches and other electrical equipment. The... Read More
Mineral transformer oil residual gas content tester TOR-8

Mineral transformer oil residual gas content tester TOR-8

GlobeCore’s TOR-8 mineral transformer oil residual gas content tester is designed to check the concentration of dissolved gases in dielectric fluid used in power transformers. Mineral oil is a well-known... Read More
Silicone transformer oil residual gas content tester TOR-8

Silicone transformer oil residual gas content tester TOR-8

The TOR-8 silicone transformer oil residual gas content tester made by GlobeCore is used to figure out the amount of dissolved gases in dielectric fluid used in power transformers, electric... Read More
Midel 7131 transformer oil residual gas content tester TOR-8

Midel 7131 transformer oil residual gas content tester TOR-8

GlobeCore’s Midel 7131 transformer oil residual gas content tester TOR-8 is designed to assess the gas composition of insulating fluid used in transformers and other electrical equipment. The monitoring of... Read More
FR3 dielectric fluid residual gas content tester TOR-8

FR3 dielectric fluid residual gas content tester TOR-8

The FR3 dielectric fluid residual gas content tester TOR-8, made by GlobeCore, is used to check the quality of insulating fluids used in transformers and other high-voltage equipment. The presence... Read More

What makes transformer oil analysis so important

The importance of analyzing transformer oil is well known and undisputed. Beside the information on the current condition of the insulation fluid, the analysis also reveals other problems: aging of... Read More
Transformer oil Degradation

Transformer Oil Degradation Analysis

Transformer oil degradation is a process caused by a number of factors. It can be the result of thermal, mechanical stresses and a few other things. Aging of transformer oil... Read More
Globecore

GlobeCore Opens a New Service Center in Costa-Rica

Dear friends! We are happy to announce that a new service center commenced operations in Costa-Rica in November 2017. This service center will assist our clients throughout the Latin America.... Read More