GlobeCore / Oil Filtration / Vacuum Oil filter Machine

Vacuum Oil filter Machine

vacuum oil filter machine

Oil degradation is a wide-spread problem in industries using oil-filled transformer equipment. There are many causes of the degrading or aging of industrial oil.

Of course, oil “ages in service”, but mostly it ages because it oxidizes, forming oxidation compounds and aging products. The rate of oxidation goes different depending on a number of factors. The first factor is – water in oil. The practice shows that oil oxidation goes faster with high water content. If water content increases double– it doubles the oxidation.

In extreme cases, transformers can fail with excessive water contamination, as it affects both the solid and liquid insulation. It decreases the breakdown strength of solid insulation, dielectric breakdown voltage of oil and the temperature of water vapor bubbles developing. Such factors make maximum loading impossible and risky unreliable operation.

The second reason is hard particles in oil that precipitate out of oil, forming sludge coatings the metal surfaces, stopping heat transfer into atmosphere. Sludge also precipitates into the pores of solid insulation again stopping heat transfer and causing partial discharges in oil with possible future breakdowns of transformers

The particles and water contaminations generate continuously causing the oil to change color from light clear whitish-yellow to dark clouded brown almost black.

Moisture and contaminants content can be controlled through oil maintenance systems- such as vacuum oil filter machines.

The GlobeCore CMM vacuum oil filter machines can be connected to off-line and on-line transformers, for dehydration in vacuum and filtration purification of transformer oil – at different processing rates depending on transformer sizes

GlobeCore CMM-0,6 – are simple in operation, portable from one site to another, easy to maintain vacuum oil filter machines having processing rates respectively 500 l / h and 600 l / h (158.82 gal/hour)

The machines dry and decontaminate insulating oil to:

  •  purification class (ISO 4406) -/14/12
  •  moisture content below 10ppm

If lower moisture content is required, or the oil is very dirty and watered– the purity can be achieved by 2-3 passes through the machine

The vacuum oil filter machine is installed to small power transformers, that are free breathing type or with a gas relay. A TSS transformer safety system securely connects the machine to an online transformer providing a reliable operation.

CMM vacuum oil filter machine operation

The oil is drawn from the lowest port of the oil tank and enters the machine, into the first filter housing that retains all the contaminants. The clean oil is heated and enters the vacuum column filled with Raschig rings to create a larger area for oil to spread to achieve space separation of water vapor and gases. A column of Raschig rings extend the travel period of the oil flow in the vacuum system to obtain the best outcome in one pass. The vapor and gas are then removed by the vacuum pump. The cleaned and dry oil passes through a final filtration in a second filter housing before returning to transformer.

The CMM vacuum oil filter machines operate in an automatic control mode with a remote monitoring via a smart phone or a PC.

Each GlobeCore vacuum oil filter machine is customized but can also include additional options as inlet and/or outlet moisture meters for the oil flow, an auxiliary vacuum pump, a trailer or a semi-trailer.

 

 

 

 

 

UVM vacuum oil filter machine

Fuel Purification Systems

The process of removing moisture and gas out of insulating oil can be improved through a double stage vacuum chamber that produces a deeper vacuum which pulls down faster providing lower gas content, enhancing the dehydration and degassing even more. Such two-stage vacuum system is installed in GlobeCore UVM vacuum oil filter machines. The UVM-4, UVM-6, UVM-10, UVM-15 are different models of one class with different design and processing rates accordingly 4000 l/h (1059 gal/hour) 6000 l/h (1588 gal/hour), 10000 l/h (2647 gal/hour), 15000 (3970 gal/hour).

The UVM vacuum filter machines are multi functional having different modes of operation

  • Oil heating and filtration
  • Oil heating, filtration, vacuum degassing/dehydration
  • Transformer vacuum degassing/dehydration

Heating filtration and vacuum dehydration degassing of oil

In the UVM vacuum oil filter machine the industrial oil at an inlet goes through a primary mesh filter that stops the large particles from getting into oil system to protect the fine filter. The oil is fed through the first filter housing then delivered into the heater. The heater supplies an optimal heating avoiding thermally breaking the oil. The heated oil enters into the double stage vacuum system including a fore-vacuum pump and high vacuum pump. In a larger vacuum tank with a larger internal area the pump down is substantially slow to drop the pressure to vaporize water vapor. The principle of a fore-vacuum pump is a to build a necessary pressure, low enough to start the high vacuum pump operating, which then has a secondary position supporting the high vacuum pump. Working together two pumps optimize drying  and degassing of insulating oil. The gas mixture is extracted and drained from the vacuum chamber. Dry oil follows the extra fine filtration in the second filter and reaches the ideal cleanliness.

After being purified all index of the insulation oil including water, gas content and fine particle size corresponding the standard specifications.

  • Water removal from 50 ppm down to 5 ppm in one pass and down to 3 ppm after several passes (measured  by the ASTM method D1533)
  • Gas removal from 10-12% down to 0.1% (measured by the ASTM method D-2945)
  • Particle removal up to 5 micron (1 micron on customer request)
  • Dielectric strength improvement to 70kV

The CMM vacuum oil filter machines remove particular matter, oxidation, moisture, water and gasses in one pass, providing clean and dry oil – constantly insuring high equipment validity, reduce spear parts cost, prolong oil life and moreover  protect the nature from thousand of liters of unhealthy oil

Heating and filtration mode

Heating and filtration mode is first used for cleaning the dirty transformer oil from polluting particles that upgrades the oil quality through a single or multi-stage filtration. It is used in cases when the oil moisture content satisfies the allowable standard levels. As some moisture is allowed in transformers to keep the solid insulation from shrinking through excessive drying. The dirty oil from equipment or container is pulled into the heater, and heated to certain temperature. The heating temperature should not exced 90 C so the oil doesn’t decompose. The filter takes out all suspended matter and some water as some of it evaporates in heating.

Secondly, heating and filtration is used during filling new oil into a transformer. The vacuum oil filter machine pulls new oil from the drum, passes it through filters, raises its temperature to near transformer temperature and fills the transformer tank. It is a generally followed practice.

Thirdly, heated filtered oil is used for hot flushing or hot oil spraying of transformer for drying the water out of solid insulation. As hot oil have high moisture absorbing qualities, leaving the core and windings totally dry. It is easy to perform, although it is very slow.

Fourthly, it is also used for heating of medium size transformers as oil goes through a continued circulation in heating and filtration mode. In this case the temperature of circulated oil is maintained at 60-70 C.

Vacuum dehydration of transformer

A mode of vacuum drying /degassing of transformers is used for on-site drying. The vacuum ensures dryness of transformer core before introducing insulating oil. The oil filter machine vacuum system consisting of 2 vacuum pumps: a fore-vacuum pump and high vacuum pump is connected to a transformer to evacuate transformer tank and pump out a vapor discharge. The evacuation process is monitored and controlled to achieve the desired levels. It is a fast and effective transformer drying procedure.

Automatic operation and additional features

The UVM machines are compact and transported on a trailer or semi-trailer to transformers or oil filled electrical equipment for servicing on-site. They are used during installation, maintenance and repair works – for filling, flushing, heating oil and transformer, evacuation, extracting solid matter, water and gas from oil.

The options include an extra vacuum assembly for transformer vacuuming, oil moisture sensors at the inlet/outlet and remote data monitoring and control.

An automatic operation is done through a PC

GC provides professional high quality vacuum oil filter machines to service power grid enterprises, transmission and distribution companies in power industry, power substations and utilities. Our mission is to create reliable equipment for the customer.

 

Leave your request